• All things technology
  • Delivery within Europe
  • Right to Cancel applies
  • Specialist retailer since 1923

Dold RK9871.72 3/N AC400/230V 50/60Hz 0062759 Voltage monitoring relay No. of relay outputs: 2

Image similar
Product type
Voltage monitoring relay
No. of relay outputs
2
Operating voltage
230 V
400 V
Type
RK9871.72 3/N AC400/230V 50/60Hz
Probe inputs
L1-L2-L3 und N
Datasheet (PDF)
EAN:
Part number:
Item no:
Sales and shipping:
Conrad ElectronicTerms & Conditions

Highlights & Details

  • Increased security in buildings

Technical specifications

  • Measuring voltage = supply voltage
  • NOMINAL VOLTAGE UN 3/N AC 400/230 V.
  • Overload capacity: 1.15 UN continuous
  • Nominal consumption: Approx. 6 VA
  • Nominal frequency 50 / 60 Hz
  • Measuring frequency range: 45 ... 65 Hz
  • Switching threshold: 195.5 V fixed
  • Hysteresis: Approx. 5%
  • Overvoltage category III (according to IEC 60664-1)
  • Accuracy ±5 %
  • Repeatability < 2%
  • Temperature influence < : 1%
  • Contact configuration: 2 changer thermal current Ith: 4 A.
  • Switching rating
  • ACCORDING TO AC 15: NORMALLY OPEN CONTACT 2 A / AC 230 V IEC/EN 60947-5-1
  • OPENER: 1 A / AC 230 V IEC/EN 60947-5-1
  • Electrical life at 1 A, 230 V AC cos ϕ: 1 x 105operations IEC/EN 60947-5-1
  • Short-circuit resistance
  • Max. Fuse 4 A GG / GL IEC/EN 60947-5-1
  • Mechanical life 1 x 206 operations
  • Temperature range:
  • Operation: - 25 ... +60 °C
  • Storage: - 25 ... 70 °C
  • Conductor mounting: Screw connection
Type

RK9871.72 3/N AC400/230V 50/60Hz

Product type

Voltage monitoring relay

No. of relay outputs

2

Probe inputs

L1-L2-L3 und N

Operating voltage

230 V

400 V

Dim

(L x W x H) 66 x 17.5 x 90 mm

Mounting depth

66

Weight

70 g

Width

17.5 mm

Height

90 mm

Length

66 mm

UKCA

yes

Documents & Downloads

Datasheet

Datasheet 2359209 Dold RK9871.72 3/N AC400/230V 50/60Hz 0062759 Voltage monitoring relay No. of relay outputs: 2

User & Safety Instructions

User & Safety Instructions 2359209 Dold RK9871.72 3/N AC400/230V 50/60Hz 0062759 Voltage monitoring relay No. of relay outputs: 2

Description


Applications:
Monitoring of three-phase power supplies for undervoltage and switching to safety power supplies.
For systems according to:
· DIN VDE 0108-100 (safety lighting)
· DIN VDE 0100-718 (structural systems for general assembly)

When the measuring voltage is applied to the measuring inputs L1-L2-L3 and the line supply is error-free, the relay switches to the good state if the voltage for 1 min. no longer falls below the undervoltage threshold.
During this waiting time of 1min, the yellow LED flashes. After detecting undervoltage at one or more phases for more than 0.5 s, the relay will drop.
The undervoltage relay measures the arithmetic mean value of the 3 phase voltages against N.

· according to IEC/EN 60255-1
· for systems according to DIN VDE 0100-718 and DIN VDE 0108-100 (following standard of DIN VDE 0108 )
· Detection of undervoltage in three-phase networks
· without separate auxiliary voltage (Generated from the measuring voltage of all 3 phases)
· LED display for operating voltage and contact position
· for any phase sequence
· Closed-circuit principle (output relay not activated in the event of a fault)
· 2 changeover contacts
· with fixed time delay of 0.5 s for error message
· with fixed time delay of 1min for switching back to good status
· with fixed response value at 195.5 V AC
· optionally with test button for function check
· 17.5 mm width

This text is machine translated.