• All things technology
  • Delivery within Europe
  • Right to Cancel applies
  • Specialist retailer since 1923

Phoenix Contact 1466607 VAL-SPP-T2-385-1+1-UT Surge arrester 20 kA 1 pc(s)

Image similar
Datasheet (PDF)
EAN:
Part number:
Item no:
Unavailable

Sales and shipping:
Conrad ElectronicTerms & Conditions

Technical specifications

  • Product family: VAL-SPP
  • IEC TEST CLASS II;T2
  • Model: Two-part rail module can be plugged
  • Number of poles: 2
  • Message Surge Protection Faulty: Optical
  • NOMINAL VOLTAGE UN 240/415 V AC ±10 % (TN-S);240/415 V AC ±10 % (TT)
  • Connection type: Forked cable lug
  • M5 screw thread
  • Tightening torque 30 lbf-in.
  • Conductor cross-section flexible: 1.5 mm² ... 25 mm²
  • Conductor cross-section rigid: 1.5 mm² ... 50 mm²;2x 1.5 mm² ... 16 mm² (2 conductors of same cross-section)
  • Wire cross-section AWG: 14 ... 2
  • Width 35.6 mm
  • Height: 96.6 mm
  • Depth: 71.5 mm (including mounting rail 7.5 mm)
  • Division unit 2 TE
  • Colour: Grey (RAL 7042);light gray (RAL 7035)
  • Flammability class according to UL 94 V-0
  • Material housing: PA 6.6-FR 20 % GF;PBT
  • Earth current IPE ≤ 5 µA
  • Nominal impulse surge current In (8/20) µs: 20 kA
  • Total leakage surge current ITtotal (8/20) µs 40 kA
  • Ambient conditions: Environmental conditions
  • Protection type: IP20C (when installed)
  • Ambient temperature (operation): -40 °C ... 85 °C
  • Ambient temperature (storage/transport): -40 °C ... 85 °C
  • Altitude: ≤ 5000 m (amsl)
  • Standards/regulations EN 61643-11
  • Note:2012 + A11:2018
  • Mounting type: Rail: 35 mm
  • EN type T2
  • POWER SUPPLY SYSTEM IEC: TN-S;TT
  • Insulation properties: Insulation properties
  • Over voltage category III
  • Pollution level 3
  • Nominal frequency FN 50 Hz (60 Hz)
  • CTI value of material: 600
  • INSULATION MATERIAL PA 6.6-FR 20 % GF;PBT
  • Material group: I
  • PROTECTION PATHS L-N;L-G;N-G
  • Standby power consumption PC: ≤ 175 MVA
  • Maximum Surge current Imax (8/20) µs 40 kA
  • Permissible air humidity (operation): 5 % ... 95 %.
  • Shock (operation): 25g (half-sine / 11 ms / 3x ±X, ±Y, ±Z)
  • Vibration (operation): 5g (10 ... 500 Hz / 2.5 h / X, Y, Z)
  • UL specifications: UL specifications
  • Maximum continuous voltage MCOV (N-G) 305 V AC
  • Power distribution system: Single phase
  • Nominal frequency 50/60 Hz
  • Measured limiting voltage MLV (N-G): 1140 V
  • SPD type 4CA
  • Stripped length: 18 mm
  • Maximum continuous voltage UC (L-N) 385 V AC
  • Maximum continuous voltage UC (N-PE) 305 V AC
  • Nominal load current IL: 80 A (25 mm²)
  • Following current extinguishing capability IFI (N-PE) 100 A
  • Short-circuit resistance ISCCR 100 kA
  • Protection level Up (L-N): ≤ 1.8 kV
  • Protection level Up (L-PE): ≤ 2 kV
  • Protection level Up (N-PE): ≤ 1.5 kV
  • Residual voltage Ures (L-N): ≤ 1.8 kV (in); ≤ 1.6 kV (at 10 kA);≤ 1.4 kV (at 5 kA);≤ 1.3 kV (at 3 kA)
  • Residual voltage Ures (L-PE): ≤ 2 kV (in); ≤ 1.7 kV (at 10 kA);≤ 1.5 kV (at 5 kA);≤ 1.4 kV (at 3 kA)
  • Residual voltage Ures (N-PE):≤ 0.5 kV (in); ≤ 0.4 kV (at 10 kA);≤ 0.3 kV (at 5 kA); ≤ 0.1 kV (at 3 kA)
  • TOV-behavior at UT (L-N): 415 V AC (5 s / resistance mode);460 V AC (120 min / safe failure mode)
  • TOV behavior at UT (N-PE): 1200 V AC (200 ms / resistance mode)
  • Response time TA (L-N): ≤ 25 ns
  • Response time TA (L-PE): ≤ 100 ns
  • Response time TA (N-PE): ≤ 100 ns
  • Maximum fusing for V-passage wiring: 80 A (gG)
  • Maximum fusing for stub cable wiring: 315 A (gG)
  • Maximum continuous voltage MCOV (L-N) 385 V AC
  • Maximum continuous voltage MCOV (L-G) 385 V AC
  • Nominal voltage: 277 V/AC
  • Measured limiting voltage MLV (L-N): 1610 V
  • Measured limiting voltage MLV (L-G): 2750 V
  • UL connection data: UL connection data
  • General: General
  • Additional technical data: Additional technical data
  • Maximum continuous voltage UC (L-PE) 385 V AC
  • Nominal leakage surge current In:20 kA
  • 2 conductors of the same cross-section flexible with TWIN cable end sleeve with plastic sleeve: 1.5 mm² ... 16 mm²
  • Conductor cross-section flexible with wire-end sleeve with plastic sleeve: 1.5 mm² ... 35 mm²;2x 1.5 mm² ... 10 mm² (2 conductors of same cross-section)
  • Conductor cross-section flexible with wire-end sleeve without plastic sleeve: 1.5 mm² ... 25 mm²;2x 1.5 mm² ... 16 mm² (2 conductors of same cross-section)
  • TOV behavior at UT (L-PE): 1464 V AC (200 ms / resistance mode)
  • Ambient temperature (mounting): -5 °C ... 50 °C
Product type

Surge arrester

Leakage current

20 kA

Nominal voltage

277 V AC

Type

Mounting rail module can be plugged in two parts

IP20C (when fitted)

Manufacturer part #

1466607

Type

2

Dim

(L x W x H) 71.5 x 35.6 x 96.6 mm

Length

71.5 mm

Width

35.6 mm

Height

96.6 mm

Depth

71.5 mm

Content

1 pc(s)

UKCA

yes

Documents & Downloads

Datasheet

Datasheet 3568539 Phoenix Contact 1466607 VAL-SPP-T2-385-1+1-UT Surge arrester 20 kA 1 pc(s)

User & Safety Instructions

User & Safety Instructions 3568539 Phoenix Contact 1466607 VAL-SPP-T2-385-1+1-UT Surge arrester 20 kA 1 pc(s)

Description

Pluggable surge arrester, according to Type 2 / Class II, for 1-phase power supply networks with separate N and PE (3-conductor system L1, N, PE).

This text is machine translated.